3.01
INSTALLATION
A.
Qualification
-
Cable
management system and accessories to be installed by the
manufacturer’s certified installation contractor to maintain
the integrity of the products and acceptable performance of
the completed installation.
B.
Inspection
1.
Examine sub-floor for unevenness, irregularities, and
dampness that would affect the quality and execution of the work.
2.
Do not proceed with installation until subfloor surfaces
are clean, dry, and clear of other trades and ready to receive
cable management system.
3.
Inspect Powerflor components for damage prior to
installation.
-
Preparation
and Installation
1.
The cable management system to be prepared and installed in
accordance with the manufacturer’s instructions covering
preparation, layout, alignment, and installation.
2.
Sub-floor shall be level within plus or minus 0.125 inches
in 10 feet, and plus or minus 0.10 inches over the entire area.
System to be installed with all components loose laid over foam
underlay, squarely and firmly on the sub-floor and free of rocking
panels.
3.
Provide cutouts, ramps, and closure trim as indicated and
as needed. Minimize the number of cut panels. Layout panels to
avoid less than ½ panel units. Scribe to accurately fit trim
pieces.
-
Adjust and
Clean
1.
Remove system installation debris as work progresses,
maintaining area under finished system floor area in a clean
condition.
2.
The general contractor is to protect the finished floor
system from damage and misuse until occupancy.
-
|