Part II – PRODUCTS
2.01 ACCEPTABLE MANUFACTURERS
Cable Management System shall be manufactured by POWERFLOR USA,
Inc. 1406 Waterford Drive – Bel Air, Maryland 21015 – Phone: (410)
893-0035 / email:
powerflorusa@aol.com Alternative products shall meet or exceed design
criteria.
2.02 MATERIAL
-
Chaseway Panel Assemblies
-
Dimensional
Requirements
Size: 18 inches by 18
inches / 50 cm x 50 cm as specified.
Dimensional Tolerances:
Edge to Edge dimension:
Plus or minus 0.015 inches.
Out of square
(difference of diagonal dimensions): 0.035 maximum.
-
Chaseway Pedestal Construction
-
Molded Polycarbonate
with UL 94V-O Flame Class rating.
-
Finish: One color.
2.03 UNDERSTRUCTURE
-
Stringerless
-
Pedestals:
9” x 9” or 25 cm x 25 cm
molded polycarbonate.
Finished Height: 2
5/8”.
-
Pedestal / Panel Assembly
1. An 18” or 50 cm
square panel assembly shall consist of four pedestals and one carpet tile
and provide a 1,000 lb. axial load without permanent deformation.
-
System Performance
1. Concentrated
Load Performance:
Panels shall be capable
of supporting a concentrated load of 1,000 lbs. placed on a one square inch
area at any location on the panel with a maximum top surface permanent set
not to exceed 0.010 inches after load is removed.
2. Uniform Load Performance:
Panels shall be capable
of supporting a minimum uniform load of 41,500 lbs. per square foot.
-
Ultimate Load
Performance:
The system shall provide
a loading capacity of not less than 1,200 lbs. per square inch, without
failure.
-
Rolling Load
Performance:
Local and overall
surface deformation shall not exceed 0.040 inches.
-
Impact Load
Performance:
Panels and supporting
understructure shall withstand without failure an impact load anywhere on
the panel of 80 lbs. dropped from a height of 36 inches onto a one square
inch area. Failure is defined as the point at which the panel will no
longer accept the load.
-
Floor Surface Covering
-
Floor panel finished
surface shall be an approved 18” or 50 cm carpet tile as indicated on
contract drawings or in this specification. Where floor coverings are
by the cable
management system manufacturer, the type, color and pattern to be
selected from
manufacturer’s standards.
-
Accessories
1.
Service outlets to be provided in locations as specified by architect
and as detailed on the contract drawings. Outlets to accommodate and
include pre-terminated power, communications and data cabling assemblies.
2.
Provide 2% spare floor panels for maintenance stock. Deliver to
project in manufacturer’s standard packages clearly marked with the
contents.
|